| Feature | Category | Specification |
|---|---|---|
| Brand & Model | Basic Info | Solis S6-EH3P20K-H (Ginlong Solis S6 Series) |
| Inverter Topology | Basic Info | Three-Phase High-Voltage (HV) Hybrid Energy Storage Inverter |
| Grid & Backup Phase | Basic Info | 3/N/PE (Three Phase) |
| Parallel Operation | Basic Info | Supported (Dual CAN-Parallel Ports Integrated) |
| Recommended Max. PV Array Power | DC Input (PV Side) | Up to 40.0 kW (Supports up to 200% DC/AC Oversizing) |
| Max. Usable PV Input Power | DC Input (PV Side) | 32.0 kW (32,000 W) |
| Max. PV Input Voltage | DC Input (PV Side) | 1000 V DC |
| Rated PV Voltage | DC Input (PV Side) | 600 V DC |
| Start-Up Voltage | DC Input (PV Side) | 160 V DC |
| MPPT Operating Voltage Range | DC Input (PV Side) | 200 V – 850 V DC |
| Number of MPPT Trackers | DC Input (PV Side) | 4 Independent MPP Trackers |
| Max. Input Strings per MPPT | DC Input (PV Side) | 1 / 1 / 1 / 1 (Total 4 DC String Inputs) |
| Max. Input Current per MPPT | DC Input (PV Side) | 20 A $\times$ 4 MPPT (Up to 4 $\times$ 20 A) |
| Battery Type Compatibility | Battery (Storage) | Lithium-ion (HV LiFePO4 / NMC) |
| Battery Voltage Range | Battery (Storage) | 120 V – 800 V DC (High Voltage Class) |
| Max. Charge / Discharge Current | Battery (Storage) | 50 A |
| Battery Ports / BMS Ports | Battery (Storage) | 1 Battery Port / 1 BMS Port (Lever Terminal) |
| Battery Communication | Battery (Storage) | CAN / RS485 |
| Rated AC Output Power (Grid) | AC Output (Grid Side) | 20.0 kW (20,000 W) |
| Max. Apparent Output Power (Grid) | AC Output (Grid Side) | 20.0 kVA |
| Rated Grid Voltage | AC Output (Grid Side) | 3/N/PE, 220 V / 380 V, 230 V / 400 V |
| Rated Grid Frequency | AC Output (Grid Side) | 50 Hz / 60 Hz |
| Rated Grid Output Current | AC Output (Grid Side) | 30.4 A / 28.9 A |
| Max. AC Input Power (Grid Side) | AC Input (Grid Side) | 30.0 kW |
| Max. AC Input Current (Grid Side) | AC Input (Grid Side) | 45.6 A / 43.3 A |
| Grid Voltage Operating Range | AC Input (Grid Side) | 304 V – 437 V / 320 V – 460 V |
| Power Factor | AC Output (Grid Side) | $>0.99$ (0.8 leading to 0.8 lagging adjustable) |
| Total Harmonic Distortion (THDi) | AC Output (Grid Side) | $< 3\%$ |
| Rated Backup Output Power (EPS) | AC Output (Backup) | 20.0 kW (20,000 W Continuous) |
| Peak Backup Overload Power | AC Output (Backup) | 1.6 times of rated power (32 kVA), 10 seconds |
| Backup Switchover Time (UPS) | AC Output (Backup) | $< 10\text{ ms}$ (Automatic Seamless Switching) |
| Three-Phase Unbalanced Load | AC Output (Backup) | Supported (Unbalanced & Half-Wave Load Handling) |
| Generator Compatibility | Auxiliary Input | Supported (20 kW Max Generator Input Power, 30.4A / 28.9A) |
| Max. Inverter Efficiency | Efficiency | 97.7% |
| EU / European Efficiency | Efficiency | 97.2% |
| DC Reverse-Polarity Protection | Protection | Integrated |
| AC Short Circuit Protection | Protection | Integrated |
| Output Over-Current Protection | Protection | Integrated |
| Surge Protection | Protection | Integrated (DC Type II / AC Type II) |
| Arc-Fault Protection | Protection | Integrated AFCI 2.0 (Optional / Supported) |
| Anti-Islanding Protection | Protection | Integrated |
| Zero-Export / Feed-in Limitation | Protection | Supported (Integrated Export Power Management) |
| Cooling Concept | General Data | Intelligent Redundant Fan-Cooling |
| Acoustic Noise Level | General Data | $< 65\text{ dB(A)}$ |
| Operating Ambient Temperature | Environmental | –25 °C to +60 °C |
| Ingress Protection | Environmental | IP66 Rated (Weatherproof & Dustproof) |
| User Interface / Display | Interface | 7.0-inch LCD Display & Bluetooth + App Control |
| Communication Interface | Connectivity | Standard: Wi-Fi + LAN + Bluetooth, CAN-BMS, CAN-Parallel $\times$ 2, RS485-Meter, RS485, DRM, DI, DO $\times$ 3 |
| DC Connection | Connectivity | MC4 Quick Connection Plug |
| Battery Connection | Connectivity | Lever Terminal |
| AC Connection | Connectivity | OT Terminal |
| Dimensions (W × H × D) | Physical Specs | $430 \times 660 \times 305\text{ mm}$ |
| Net Weight | Physical Specs | Approx. 35.2 kg |
| Warranty | After-Sales | 05 Years Official Manufacturer / Authorized Warranty |
Solis S6-EH3P20K-H 20kW Three Phase Hybrid Solar Inverter
The Solis S6-EH3P20K-H is a high-performance 20kW Three-Phase High-Voltage (HV) Energy Storage Hybrid Solar Inverter with 4 MPPT Trackers (4 DC String Inputs) engineered for commercial business properties, manufacturing units, hospitals, and expansive three-phase estates. Delivering a continuous rated AC output power of 20.0 kW (20 kVA on-grid and backup), it incorporates a high-efficiency high-voltage 120V–800V battery interface supporting up to 50A charge/discharge current. The solar DC input accommodates up to 40.0 kW maximum PV array size (32.0 kW usable PV power) across 4 independent MPPTs handling up to 20A continuous input current per string. Equipped with rapid UPS-grade transfer switching (<10ms) for continuous backup during utility outages, 10 seconds of 160% surge overload capability, support for 100% unbalanced and half-wave loads, dedicated 20kW generator connectivity, integrated Zero-Export grid feed-in management, an IP66-rated weather-sealed enclosure, and scalable parallel expansion, it delivers industrial-grade power autonomy and load protection.
310,000৳
Cash / Online Price
Online / Cash Payment
27,083৳/month
Regular Price: 325,000৳
0% EMI up to 12 Months
Specification
Description
Solis S6-EH3P20K-H 20kW Three Phase Hybrid Solar Inverter
Designed for commercial corporate headquarters, spinning and garment units, medical clinics, cold storage facilities, and high-demand three-phase residential estates connected across standard 380V/400V utility networks, the Solis S6-EH3P20K-H represents Ginlong Solis’s dedicated 20kW commercial high-voltage energy storage inverter platform. It coordinates power flow between rooftop solar arrays, high-voltage battery storage racks, the public utility grid, and on-site auxiliary diesel or gas generators.
The solar DC input architecture features 4 Independent Maximum Power Point Trackers (MPPT) with 4 DC string inputs. Supporting up to 40.0 kW of recommended DC array capacity (up to 32 kW usable PV input), the system operates across an MPPT voltage window of 200V to 850V (start-up at 160V) with a maximum voltage ceiling of 1000V DC. Supporting up to 20A continuous DC input current per MPPT, it pairs smoothly with modern high-power 550W+ to 700W+ bifacial modules without string clipping. The 4-MPPT configuration gives EPC engineers design freedom across complex multi-pitch roofs, varying tilt planes, and multi-directional orientations without mismatch yield losses.
The energy storage subsystem utilizes a high-efficiency high-voltage battery architecture from 120V to 800V DC, reducing resistive $I^2R$ transmission losses and cabling thickness compared to traditional low-voltage setups. Supporting up to 50A continuous charge and discharge current, it is compatible with leading commercial high-voltage Lithium-ion (HV LiFePO4) battery systems. The inverter natively supports unbalanced and half-wave three-phase loads on both grid and backup outputs, allowing commercial facilities to power single-phase heavy machinery and office equipment across separate phases without triggering voltage imbalance faults.
During utility grid failures, the internal automatic transfer switch engages in less than 10 milliseconds (<10ms), keeping critical servers, network hardware, laboratory instruments, and industrial refrigeration operating without interruption. A 10-second 160% surge envelope (32 kVA) reliably absorbs high inductive motor startup spikes from compressors, central air conditioners, and heavy water pumps. Built inside an IP66-certified weather-sealed enclosure weighing 35.2 kg, the inverter ensures thermal stability under heavy ambient loads and operating temperatures from –25 °C to +60 °C. System management is handled locally via a 7-inch LCD screen with Bluetooth app commissioning and remotely through SolisCloud via CAN-BMS, dual CAN-Parallel ports, RS485, and standard Wi-Fi / LAN connectivity.
Product Pricing & Availability
The retail price for the Solis S6-EH3P20K-H 20kW Three Phase Hybrid Solar Inverter in Bangladesh typically ranges between 310,000৳ and 325,000৳ (with current promotional cash pricing at 310,000৳ against regular showroom list prices reaching 325,000৳).
Turnkey commercial and industrial hybrid solar engineering, high-voltage LiFePO4 battery storage integration, Tier-1 bifacial solar PV modules, heavy-duty mounting structures, AC/DC combiner switchgear, and professional installation services are fulfilled directly through International Office Solution.
What is the price of Solis S6-EH3P20K-H 20kW Three Phase Hybrid Solar Inverter in Bangladesh?
The latest price of Solis S6-EH3P20K-H 20kW Three Phase Hybrid Solar Inverter in Bangladesh is 310,000৳. You can buy the Solis S6-EH3P20K-H 20kW Three Phase Hybrid Solar Inverter at best price from our website or visit any of our showrooms.
Questions (0)
Have question about this product? Get specific details about this product from expert.
Reviews (0)
Get specific details about this product from customers who own it.